Continuous power protection for critical loads. Our UPS systems and inverters deliver clean, reliable AC power from DC battery systems.
“The TECNED ONV(D) UPS series is available with single phase and three phase input and single phase output with ratings up to 100 kVA in a single enclosure. The ONV (D) series can be configured to charge common battery types from VRLA to NICAD.
The ONV (D) series can be supplied as standard or fault tolerant systems within a single enclosure to meet customer requirements for safety and reliability.
The ONV-D model includes an additional digital controller with LCD display that shows the systems current state of operation and system values, allows setting of system parameters and includes event and alarm logs.
Option list ONV (D)
Additional options ONV (D)
| Input | Voltage single phase | 110/120/200/220/230/240/277V, (2W+E) |
| Voltage three phase | 208/220/240/380/415/480V, (3W+E) | |
| Voltage tolerance | + 15% / – 20% (-20% start battery operation) | |
| Frequency | 50Hz / 60Hz +/- 10% | |
| Harmonic distortion | < 5% THDI | |
| Power Factor | 0.99 | |
| Battery | Voltage (nominal) | 24 / 48 / 110 (125) / 220 Vdc |
| Characteristic | I-U according to DIN 41773 | |
| Output | Voltage | 110/120/200/220/230/240/277V+N |
| Static stability | +/- 1% | |
| Voltage THD | Max 1.5% for 100% linear load | |
| Frequency | 50Hz / 60Hz (selectable) +/- 0.1% (free running) | |
| Power factor | 0.9 PF Lag | |
| General | Ambient temperature | -20 to +70 °C storage / -10 to +40 °C operation |
| Altitude above sea level | 1000 m | |
| Enclosure | Aluzinc frame / powder coat RAL 7035 | |
| Standards | Safety IEC/EN 62040-1 / EMC 55011 | |
| Conformity | IEC 60146 / CE-Label |